Gutter Snow-Melting Heating Cable
Heat Tracing Products

Gutter Snow-Melting Heating Cable

The gutter snow-melting heating cable uses a parallel self-regulating heating core cable, which can be installed along eaves, roof drainage paths, gutters, and downspouts. When covered with ice and snow, the cable automatically increases output to form a continuous drainage channel, and reduces output once the surface is dry; used together with temperature, humidity, or ice-and-snow controllers, it can automatically start and stop according to actual weather conditions.

Rated Voltage
110–120V or 208–277V AC
Rated Output in Snow and Ice (0°C)
39 W/m
Rated Output in Dry Air (0°C)
20 W/m
Minimum Bending Radius
32 mm

Product highlights

  • Specifically designed for snow and ice melting on eaves, gutters, downspouts, and roof drainage paths.
  • The self-regulating heating core cable adjusts heating output section by section according to ice and snow coverage and ambient temperature.
  • Parallel circuits can be cut according to the on-site layout path within the allowable circuit length.
  • Tin-plated copper braid provides a grounding path, and the UV-resistant outer sheath is suitable for outdoor exposure.
  • Can be used with temperature and humidity or ice-and-snow sensors to reduce operating energy consumption when there is no ice or snow.

Technical specifications

Rated Voltage
110–120V or 208–277V AC
Rated Output in Snow and Ice (0°C)
39 W/m
Rated Output in Dry Air (0°C)
20 W/m
Minimum Bending Radius
32 mm
Conductive Bus
Approximately 1.3 mm ² Nickel-Plated Copper Conductor
Heating Core Tape
Irradiation Cross-Linked Polyolefin self-regulating Heating Core Tape
Insulation layer
Irradiation cross-linked polyolefin insulation
Metal braid layer
Tin-plated copper braided grounding layer
Outer sheath
Polyolefin outer sheath with UV-resistant additives
Applicable Areas
Eaves, roof drainage paths, gutters, and downspouts
Circuit Design
Determined according to power supply voltage, starting temperature, circuit breaker capacity, and wiring route
Control and Protection
Equipped with ice and snow controllers, and set 30mA ground fault protection for each branch
Heat Tracing Products
Back to products
Low-Temperature Self-Regulating Heat Tracing Cable
01

Low-Temperature Self-Regulating Heat Tracing Cable

The low-temperature self-regulating heat tracing cable uses two parallel bus wires and a PTC semiconductor polymer heating core tape. The core tape automatically adjusts output according to local pipe temperature changes: power increases when the temperature drops and decreases when the temperature rises. It is suitable for freeze protection, anti-freezing, and maintaining process temperatures up to 65°C for pipelines, valves, tanks, and equipment in water supply and drainage, fire protection, petrochemical, and other industries.

  • PTC core tape adjusts heating output segment by segment, adapting to different heat dissipation at various pipe positions
  • Parallel busbar structure, can be cut to installation size within the specified maximum loop length
  • self-regulating feature reduces the risk of continuous overheating at overlapping installation positions
Medium-Temperature Self-Regulating Heat Tracing Cable
02

Medium-Temperature Self-Regulating Heat Tracing Cable

The medium-temperature self-regulating heat tracing cable uses parallel bus wires and PTC semiconductor polymer heating core tape, which can automatically adjust the output according to local temperature changes of the pipeline. It is suitable for antifreeze, anti-condensation, and 0–105°C process temperature maintenance of industrial pipelines, valves, storage tanks, and equipment in petroleum, chemical, steel, and power industries.

  • The PTC core tape adjusts the heating output in segments to compensate for heat loss variations at different positions of the pipeline.
  • The parallel loop structure allows cutting according to installation size within the specified maximum loop length.
  • 35 / 45 / 50 / 60 W/m power levels cover medium-temperature antifreeze and process temperature maintenance requirements.
High-Temperature Self-Regulating Heat Tracing Cable
03

High-Temperature Self-Regulating Heat Tracing Cable

The high-temperature self-regulating heat tracing tape uses a semiconductor self-regulating heating core tape and parallel circuits that can be cut on-site. It automatically adjusts output along the heating loop according to ambient temperature and thermal loss of the insulation layer. It is suitable for frost protection and maintaining a process temperature up to 150°C for high-temperature process pipelines, valves, instrument lines, storage tanks, and equipment, and can withstand intermittent high temperatures caused by steam purging.

  • The semiconductor heating core tape adjusts output section by section along the loop to compensate for local heat loss changes.
  • The parallel loop structure allows cutting to on-site dimensions within the specified maximum loop length.
  • 10 / 20 / 30 / 39 / 49 / 66 W/m power ratings cover different high-temperature maintenance loads.

Need help confirming selection or project parameters?

Send the operating environment, temperature, dimensions, and power conditions so we can help confirm the fit.

Request RFQ